API 624:2014 pdf free download

API 624:2014 pdf free download

API 624:2014 pdf free download.Type Testing of Rising Stem Valves Equipped with Graphite Packing for Fugitive Emissions
4.1The APIl 622 certificate or test report for the packing in the test valve shall be provided and attached to the APl624 fugitive emissions test report.
4.2The test valve shall be completely assembled and ready for testing. The test valve shall be randomly selectedfrom manufacturer or distributor stock where such stock is available. For valves not in stock, the manufacturer shallcertify that the test valve was not modified in any way to meet type test requirements and is a typical representation ofthe manufacturer’s stock product. Valve selection shall be approved by the purchaser.
4.3 Body-bonnet and gland bolting torque shall be verified to be in accordance with published manufacturer’sinstallation specifications.
4.4 All pre-test activities to the valve shall be documented on the Fugitive Emissions Test Report in Annex A.4.5 As a safety precaution, the air in the valve cavity shall be purged with an inert gas prior to starting the testing.5Type Testing
5.1The test medium used shall be methane 97 % minimum purity.
Caution—Methane used during testing is a pressurized flammable gas which requires that appropriate safetymeasures be taken.
5.1.1Testing of valves is potentially hazardous and it is essential that the safety of personnel be given primeconsideration. Given the nature of this test, hazardous release of pressurized gas could occur.Adequate shields orbarriers in the area of the test enclosure and other appropriate means for the protection of personnel shall beprovided.
5.1.2 The test facilities shall be designed to ensure that all the test conditions are conducted in a safe and protectedenvironment. lt is the responsibility of the testing facility to analyze the hazards resulting from the pressure andtemperatures and take proper safety precautions.All applicable safety regulations shall be complied with.
5.1.3 All equipment shall have appropriate certfication that verifies its suitability to withstand the minimum andmaximum pressures and temperatures in the testing environment.
5.1.4 Hoses or pipes used for inlet and outlet supply of methane shall be suitable for maximum pressures andtemperatures.Where hoses are used, appropriately designed restraints shall be used to prevent hose detachmentfrom the test rig in the event that a blow-out occurs.
5.1.5 All testing shall be in accordance with local and national codes and regulations.5.2The stem orientation for a test valve shall be vertical.
5.3Valves shall be subjected to a total of 310 mechanical cycles and 3 thermal cycles per Figure 1.Mechanicalcycling shall begin with the valve at ambient temperature. An optional low temperature test at -29 C(-20 °F) may beperformed if requested by the purchaser (see Figure 1).
5.4The valve shall be heated using an internal heat source or an external heat source such as electric heatingblanket, coils, or other suitable equipment or an appropriate internal heat source.
5.5 The elevated test temperature shall be 260°C (500 °F) +5 percent.
5.6 The test pressure shall be the lower of 41.4 barg (600 psig) or the maximum allowable pressure at 260 °C(500 °F) per ASME B16.34 for the applicable material group and shall be held constant throughout the test.
5.7 The test valve may be equipped with a method of actuation capable of mechanically cycling the valve. The method of actuation should not impose additional side loads on the stem or packing. Running torque values shall be recorded on the first and last cycle of testing.
5.8 Static and dynamic stem leakage measurements shall be taken. See Figure 1.
5.8.1 Leak measurements shall be conducted in still air. Shielding potential leak paths from environmental impacts with a foil enclosure shall be employed during testing. The foil enclosure shall include the stem outside diameter and packing outside diameter.
5.8.2 Leak measurements of the body-bonnet connection and auxiliary connections shall be sniffed. Leakage from body-bonnet and auxiliary connections can affect leak measurement readings and shall be corrected prior to continuation of the test and noted in the report. The detector probe speed shall be approximately 25 mm (1 in.) per second for the bonnet. The instrument shall be adjusted to compensate for the background methane level.
5.8.3 The static/dynamic leakage shall be recorded after a time delay of twice the response time of the instrument.
5.9 The valve shall be equipped with thermocouples for monitoring the temperature during testing. The temperature shall be monitored and recorded at two locations (see Figure 2).
5.9.1 TC-1—affixed to the stuffing box. The thermocouple affixed to the stuffing box shall control the test temperature.API 624 pdf download.API 624:2014 pdf free download

Leave a Reply

Your email address will not be published. Required fields are marked *